DKG-109 AUTOMATIC MAINS FAILURE UNIT


The DKG-109 is a comprehensive AMF unit for a single genset standby or dual genset mutual standby operations.

The standard model has MPU inputs. The DKG-109J model has CANBUS inputs.

The operation of the unit is controlled with front panel pushbuttons. The RUN, AUTO and STOP pushbuttons select the operating mode. Other buttons select the display parameter scroll, alarm mute and lamp test functions.

The DKG-109 provides a comprehensive set of digitally adjustable timers, threshold levels, input and output configurations and operating sequences.

The unauthorized access to program parameters is prevented by a 3 level password protection. All programs may be modified via front panel pushbuttons, and do not require an external unit.

The fault conditions are considered in 3 categories as Warnings, Load dumps and Shutdown Alarms. Measured values have separate programmable limits for warning and shutdown conditions.

The unit is able to send SMS messages in fault conditions.


Karşılaştır

Features

  • True RMS measurements
  • Automatic mains failure
  • Engine control
  • Gas engine support
  • Engine idle speed control
  • Generator protection
  • Built in alarms and warnings
  • Magnetic pickup input
  • Remote Start operation available
  • Dual genset mutual standby operation
  • Load shedding, dummy load
  • Periodic maintenance request monitoring
  • Event logging with measurements
  • Statistical counters
  • Field adjustable parameters
  • Logic level serial port
  • Firmware downloadable from serial port
    Free MS-Windows Remote monitoring SW:
  •     -monitoring and control
  •     -download of parameters
  •     -upload of parameters
  • GSM SMS message sending on fault
  • MODBUS communications
  • Graphic LCD display (128×64 pixels)
  • User friendly graphic indicators
  • Triple language support
  • Customer logo display capability
  • Protected semiconductor digital outputs
  • Configurable analogue inputs: 3
  • Configurable digital inputs: 5
  • Configurable relay outputs: 2
  • Total relay outputs: 6
  • Survives cranking dropouts
  • Sealed front panel
  • Plug-in connection system for easy replacement